90
Adjustment and commissioning
Detailed procedure for teach-in by flow rate
→ Choose the flow rate unit in which teach-in is run:
Mx:Inputs
Calibration
DI1/2: FlowM0:Inputs
Flow unitFlow teaching
L/h
Igal/s
...
→ Run teach-in by flow rate:
→ Allow the fluid to circulate in the pipes and wait
for the flow rate to stabilise.
The multiCELL displays the K factor
calculated by teach-in.
OK
OK
OK
The multiCELL displays the flow rate
calculated with the current K factor
→ Enter the value of the flow rate
in the pipe.
0049 L/min
0001 L/s
Flow teaching
Calibration
DI1:/DI2:FlowM0:Inputs
Start teaching
Meas. in progr.
Average flow
Flow K factor:
K=3,810
Teaching result
0005 L/min
The multiCELL calculates the flow rate
measured in the pipe, with the current K factor,
for 100 seconds
1)
.
The bargraph shows the time passed.
1)
Measurement can be suspended at any time by clicking on "OK".
Type 8619
english