Adjustment and commissioning
Connect the analogue input AI1 or AI2 to the current or voltage analogue output of an external instrument (for
instance, the 4-20 mA output of a pressure measuring device type 8311).
The analogue input signal is adjusted (slope and offset) and the multiCELL
displays the input calibrated value.
Generate a 4 mA current on the 4-20 mA output of the instrument con-
nected to the analogue input.
Enter 4 mA.
Wait for the measurement to stabilize.
Calibration Mx:Inputs Current calibr.
OK
F4
1st point
4.001 mA
4.000 mA
Calibrate using a
2nd point?
NO
2nd point
20.001 mA
20.000 mA
Generate a 20 mA current on the 4-20 mA output of the instrument con-
nected to the analogue input.
Enter 20 mA.
Wait for the measurement to stabilize.
OK
F4
YES
The multiCELL adjusts the
offset.
AI1/AI2
Value received on the analogue input.
Calibration result
16.02 mA
SAVE
F4
Figure 69 : Example for the calibration of an analogue input with respect to the current output of a pressure measuring
device type 8311
Type 8619