43
AS-Interface installation
10.6.1 Status LED yellow
LED yellow
flashing Teach function is running
flickers
Puck PCB or puck not available
→ Insert puck PCB or puck.
Table 9: Status LED yellow - AS-Interface
10.6.2 Valve LED yellow
The yellow LED (valve) indicates whether the pilot valve is actuated (LED is lit yellow).
10.6.3 Bus LED red and green
The red and green LEDs (bus) indicate the bus status:
LED green LED red
off off POWER OFF
off on No data traffic (expired Watch Dog at slave address does not equal 0)
on off OK
flashing on Slave address equals 0
off flashing Sensor supply overloaded or external reset
Table 10: LED bus status - AS-Interface