8625-2 Standard - 25
english
6.6.4
AMPL
- setting the amplification Kp
Î Select the amplification factor K
P
in a range from 0.00 to 10.00 %/K (factory
setting: 1.00). If it is attempted to set a higher value, the display will jump
automatically to 0 and a value must be entered within the range.
Setting aid:
If excessive overshoot occurs at the value of K
P
set or the control
becomes unstable, you should decrease K
P
.
On the other hand, unsatisfactory control dynamics may be improved by
raising K
P
as long as the abovementioned instability does not occur.
increase digit
next digit
2 s set decimal point
Fig.: Setting the amplification K
P