16
Rotary actuators with integrated emergency reset
Specify end positions
All positions are now saved.
Disconnect the card from the power
supply.
8.8 Normal operation
Display normal operation
G
Switch on card.
The GREEN LED lights up 3x to indicate that the
start process has been implemented correctly.
G
In normal operation the GREEN LED lights up
when the rotary actuator opens the shut-off valve.
R
The RED LED lights up when the rotary actuator
closes the shut-off valve.
G
R
If neither of the LEDs is lit, the actuator is not
actuated.
G R
The RED and the GREEN LEDs light up if the
torque is too high and the rotary actuator stops.
Change direction of rotation of the rotary
actuator or switch over the voltage OPEN/
CLOSED to restart the rotary actuator!
9 ROTARY ACTUATORS WITH
INTEGRATED EMERGENCY RESET
9.1 Technical data
Voltage 18 V DC
Currant nominal 0.8 A
Max. current 2.4 A
Charging time max. 14 h
Feedback relay for charge state 24 V DC - 1 A max
Permitted ambient temperature -10 °C - +40 °C
9.2 Electric wiring
65
F+
E-
66
17
18
17
18
Battery block
Control and power
supply card
F+
Wire colour
red
E-
Wire colour
black
Load state
feedback
Loaded battery: closed
contact
1 2 3 1 2 3
D1
D2
Open
N
Ph
A
A
Ph
Open
KM1
N
A1
A2
N
24 V
AC/DC
B
B
100V-240V 50/60 Hz
(100V-350V DC)
15V-30V 50/60 Hz
(12V-48V DC)
On / Off Mode
KM1 - Customer
contactor switch
Suggestet customer
wiring
Actuator
wiring
Total security mode
Safety block
Fig. 10: Electric wiring