16
Rotary actuators with integrated emergency reset
Specify end positions
All positions are now saved.
→ Disconnect the card from the power
supply.
8.8 Normal operation
Display normal operation
G
→ Switch on card.
The GREEN LED lights up 3x to indicate that the
start process has been implemented correctly.
G
In normal operation the GREEN LED lights up
when the rotary actuator opens the shut-off valve.
R
The RED LED lights up when the rotary actuator
closes the shut-off valve.
G
R
If neither of the LEDs is lit, the actuator is not
actuated.
G R
The RED and the GREEN LEDs light up if the
torque is too high and the rotary actuator stops.
→ Change direction of rotation of the rotary
actuator or switch over the voltage OPEN/
CLOSED to restart the rotary actuator!
9 ROTARY ACTUATORS WITH
INTEGRATED EMERGENCY RESET
9.1 Technical data
Voltage 18 V DC
Currant nominal 0.8 A
Max. current 2.4 A
Charging time max. 14 h
Feedback relay for charge state 24 V DC - 1 A max
Permitted ambient temperature -10 °C - +40 °C
9.2 Electric wiring
65
F+
E-
66
17
18
17
18
Battery block
Control and power
supply card
F+
Wire colour
red
E-
Wire colour
black
Load state
feedback
Loaded battery: closed
contact
1 2 3 1 2 3
D1
D2
Open
N
Ph
A
A
Ph
Open
KM1
N
A1
A2
N
24 V
AC/DC
B
B
100V-240V 50/60 Hz
(100V-350V DC)
15V-30V 50/60 Hz
(12V-48V DC)
On / Off Mode
KM1 - Customer
contactor switch
Suggestet customer
wiring
Actuator
wiring
Total security mode
Safety block
Fig. 10: Electric wiring