7.3.3. Wiring the input module "INPUT"
The "INPUT" inputs module has:
Two analogue inputs;
Two digital inputs.
The inputs are galvanically insulated, and therefore voltage free.
+-
+-
1
A+
A-
A+
A-
FE
D+
D-
D+
D-
0 VDC
12-36 VDC
12-36 VDC
0 VDC
2 3 4 5 6 7 8 9
(AI1) (AI2) (DI1) (DI2)
5-36 VDC
0 VDC
-
+
5-36 VDC
0 VDC
2nd digital output (at
external instrument)
1st digital output (at
external instrument)
1st 0/4-20 mA output (at
external instrument)
2nd 0/4-20 mA output (at external instrument)
digital inputs
analogue
inputs
(designation in the configuration menus of the Mx
input module)
FE = functional earth
Figure 8 : Connecting the analogue inputs to a 2-wire current transmitter and connecting the digital inputs of the input
module