Technical data
NOTE!
Avoid heat sources which may result in the permitted tempera-
ture range to be exceeded.
6.5. Identification
The rotary actuator is fitted with a rating plate which uniquely identifies
the device and indicates the most important technical data.
Do not remove the rating plate from the rotary actuator!
It is essential for identification when installing and ser-
vicing the device.
The warranty is void without the rating plate.
6.5.1. Location of the rating plate
Rating plate
Fig. 3: Location of the rating plate
6.5.2. Description of the rating plate
Labelling rating plate:
FLUID CONTROL SYSTEMS
G 74653 INGELFINGEN
Type : 3004 182 384
Serial n° : 086417 001
90 ° 75 Nm 20 s
24 V AC/DC Hz 45 W
Year : 2007
CE conformity
Actuating time 90°
Date of manufacture
Protection class
Torque
Power consumption
Type designation
Serial number
Rotation angle
Operating voltage
Current type
Fig. 4: Description of the rating plate
Labelling ATEX-rating plate:
II 2 G D
Ex d IIB T5 tD A21
IP 67 T95°C
WARNUNG / WARNING / AVERTISSEMENT
Ne pas ouvrir en zone explosible
Do not open in explosive area
Nicht in explosiver Zone öffnen
Ne pas ouvrir sous tension
Do not open while energized
Nicht unter Spannung öffnen
LCIE 07 ATEX 6078X
0102
II 2
G
D
Ex d IIB T5 tD A21
Inspection body
Device group
Ignition protection type
Device category
Zone
Temperature class (gas)
IP
67 T95°C
Explosion group
Ignition protection type
Max. surface temperature
Protection class
Licence number
Fig. 5: Example of ATEX rating plate