Operating Instructions Type 6516
Design:
3-way solenoid valve, internally piloted
Seal Materials and Fluids handled:
See Table 1.
Fluid and Ambient Temperature:
For Hazardous Locations Div. 1 (T4 rated)
Max. Ambient Temperature 104 °F (40 °C)
Max. Fluid Temperature 140 °F (60 °C)
For Hazardous Locations Div. 1 (T6 rated)
Max. Ambient Temperature 104 °F (40 °C)
Max. Fluid Temperature 140 °F (60 °C)
For Intrinsically Safe Apparatus for use in Class I, II and III,
Division 1 Hazardous Locations.
Max. Ambient Temperature 140 °F (60 °C)
Max. Fluid Temperature 140 °F (60 °C)
For Hazardous Locations Div. 2 and Ordinary Locations:
See Table 1.
Pressure Range:
Maximum inlet pressure see label on valve.
Installation:
Before installing valve ensure that piping etc. is free of foreign
matter (metal shavings, pipe sealing materials, welding scale
etc.). Installation as required but preferable with coil uppermost.
Installation in this position tends to prevent foreign matter
remaining in core tube (increased life). Do not put any loads on
coil unit.
PTFE tape is recommended for sealing ports. Mounting is
accomplished by means of four M4 x 8 mm tapped holes
located on the valve underside. Letters on valve body indicate
pressure port, exhaust and outlet of the valve.
Marking (example):
Body Material
PA = Polyamide
AL = Aluminium
Seal Material
PB = NBR and PUR
NBR = NBR
Circuit function
C = 3-way, Normally Closed
D = 3-way, Normally Open
Item No.
Voltage / Frequency / Power Consumption
Maximum Pressure
Approvals
The valve is either approved as
General Purpose valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 4
or
General Purpose valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 6
or
Intrinsically Safe Apparatus for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 6
or
FM approved as
Nonincendive for Hazardous Locations
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 1 and 2
Operating Temperature T 4
UL listed for General Purpose
CSA approved for General Purpose
See label on the valve.
Table 1 Seal Materials
Fluid Temperatures [°F] PB Buna “N”
NBR
Air Fluid Temp. + 10 to +122 + 10 to +122
Ambient + 10 to +130 + 10 to +130
Operating Instructions 0605/10_EU-EN_00801864
Voltage 12V or 24V
UL / UR valid with
class 2 power supply only